El contenido a continuación está en inglés

Centrifugal fans / blowers maximize static pressure to provide concentrated airflow in one defined direction. These blowers can be used in a fixed position or mounted on moving parts, and are optimal for local cooling and airflow through ducts.

 

Unit of Measure

Fan Type

- Centrifugal Fan / Blower

Impeller Diameter

- 3.15 in.80 mm

Power Supply

- Single-Phase 200/220/230 VAC

Current (A)

- 0.14 [200 VAC, 50 Hz]
0.18 [200/220/230 VAC, 60 Hz]
0.15 [230 VAC, 50 Hz]

Speed (r/min)

- 2800 [200 VAC, 50 Hz]
2850 [230 VAC, 50 Hz]
3200 [200 VAC, 60 Hz]
3350 [220/230 VAC, 60 Hz]

Max. Air Flow

- 56.5 CFM [200/230 VAC, 50 Hz]
63.5 CFM [200/220/230 VAC, 60 Hz]  
1.6 m3/min [200/230 VAC, 50 Hz]
1.8 m3/min [200/220/230 VAC, 60 Hz]  

Max. Static Pressure

- 0.61 inH2O [200 VAC, 50 Hz]
0.63 inH2O [230 VAC, 50 Hz]
0.886 inH2O [200 VAC, 60 Hz]
0.906 inH2O [220/230 VAC, 60 Hz]  
152 Pa [200 VAC, 50 Hz]
157 Pa [230 VAC, 50 Hz]
221 Pa [200 VAC, 60 Hz]
226 Pa [220/230 VAC, 60 Hz]  

Noise Level

- 55 dB (A) [200/230 VAC, 50 Hz]
58 dB (A) [200 VAC, 60 Hz]
59 dB (A) [220/230 VAC, 60 Hz]

Fan Kit

- Fan Only

RoHS Compliant

- Yes

Safety Standards

- UL CSA CE

CE Marking

- Low Voltage Directives

Insulation Resistance

- 100 M Ω or more when 500 VDC is applied between the windings and the frame under normal ambient temperature and humidity.

Dielectric Strength

- Sufficient to withstand 1.5 kV at 50Hz applied between the windings and the frame for 1 minute under normal ambient temperature and humidity.

Temperature Rise

- 81°F (45°C) or less measured by the thermometer method after the temperature of the motor case has stabilized after continuous operation under normal ambient temperature and humidity.

Insulation Class

- Class E (248°F [120°C]), Recognized as Class A (221°F [105°C]) by UL and CSA standards.

Overheat Protection

- Built-in thermal protector (automatic reset type)
Operating temperature, open: 248°F±9°F (120°C±5°C), close: 170.6°F±27°F (77°C±15°C)

Ambient Temperature Range

- 14°F ~ 122°F (-10°C ~ 50°C)

Ambient Humidity

- 85% or less (noncondensing)


 


 


 


 